Specifications

Standby Rating 200 ekW
Frequency 60 Hz
Emissions/Fuel Strategy U.S. EPA Tier 3 Certified
Voltage 208 to 600 Volts
Speed 1800 rpm
Duty Cycle Standby
Engine Model C7.1 I-6, 4-Cycle Diesel
Bore 4.1 in105 mm
Stroke 5.31 in135 mm
Displacement 428 in³7.01 l
Compression Ratio 16.7:1
Aspiration Turbocharged, Air to Air Aftercooled
Fuel System Electronic, Common Rail
Governor Type ADEM™A4
Length - Maximum 103.7 in2634 mm
Width - Maximum 51.2 in1300 mm
Height - Maximum 58.7 in1492 mm
Dry Weight - Genset (maximum) 3917 lb1777 kg

Key Features

Cat Generator Set Package

        

  • Cat generator set packages have been fully prototype tested
  •     

  • Meets NFPA 110 loading requirements
  •     

  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

        

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  •     

  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

Designed to meet applicable global standards including ISO 8528, ISO 3046 and IEC 60034-1, with CSA, UL2200, IBC, NEMA and NFPA conformity available depending on configuration and market.

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Equipment

Standard Equipment

Air Inlet System

  • Air cleaner; light duty with disposable element

Control Panels

  • GCCP 1.2

Cooling System

  • Coolant drain line with valves
  • Radiator and cooling fan with guards
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive

Fuel System

  • Standard open set fuel tank wide base

Lube System

  • Oil drain line with valve
  • Lubricating oil

Mounting System

  • Captive linear vibration isolators
  • Includes lifting provision and drag points
  • Termination points for coolant and lube oil drain lines

Starting / Charging System

  • 24V battery with rack and cables

Governing System

  • Cat electronic governor ADEM A4

General

  • Engine and alternator pre-paint, Caterpillar yellow

Telematics

  • Cat® Product Link™ PL444 cellular

Optional Equipment

Alternator System

  • Battery disconnect switch
  • SE, AREP, PMG Excitation
  • Anti-condensation heater
  • Mounting & Duct plate

Circuit breakers

  • Single / Multi manual circuit breakers

Exhaust System

  • 10,25,35 dBA mufflers / Enclosure muffler

Control Panel Options

  • Panel mounted audible alarm
  • NFPA 110 bundle
  • Emergency stop with key
  • Earth fault (2 wire only)
  • I/O Expansion module

Control System

  • Current transformer
  • Volt free contacts for common alarm
  • Static battery charger

Cooling System

  • Low coolant temperature
  • Jacket water heater
  • Low coolant level shutdown

Enclosures

  • Sound attenuated level 2 enclosure

Fuel Systems

  • 24 hrs integral fuel tank
  • Low fuel level alarm
  • Fuel vent pipe / Vent pipe extention
  • High fuel level alarm

General

  • Stone guards/radiator trans flange

Certifications

  • IBC Seismic, UL2200

Power Termination

  • Circuit breaker, Neutral bars, Shunt trips
360° Interior View (HTML)