D250 GC (60 Hz) Generator Set

Share

Description

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Manufacturer: CAT

Brochures & Links

Specifications

Download Specification Sheets

Specifications

Standby Rating 250 ekW
Frequency 60 Hz
Emissions/Fuel Strategy U.S. EPA Tier 3 Certified
Voltage 208 to 600 Volts
Speed 1800 rpm
Duty Cycle Standby
Engine Model Cat® C9 In-line 6, 4-cycle Diesel
Bore 4.4 in112 mm
Stroke 5.9 in149 mm
Displacement 538 in³8.8 l
Compression Ratio 16.3:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel System HEUI
Governor Type Adem™A4
Length - Maximum 155.5 in3950 mm
Width - Minimum 56.3 in1430 mm
Width - Maximum 56.7 in1440 mm
Height - Minimum 67.2 in1706 mm
Height - Maximum 86.7 in2202 mm
Dry Weight - Genset (minimum) 5324.2 lb2415 kg
Dry Weight - Genset (maximum) 6735.1 lb3055 kg

Key Features

Cat Generator Set Package

        

  • Cat generator set packages have been fully prototype tested
  •     

  • Meets NFPA 110 loading requirements
  •     

  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to104°F (40°C)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

Designed to meet applicable global standards including ISO 8528, ISO 3046 and IEC 60034-1, with CSA, UL2200, IBC, NEMA and NFPA conformity available depending on configuration and market.

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Equipment

Standard Equipment

Air Inlet System

  • Air cleaner - Non canister, disposable

Control Panel

  • GCCP 1.2

Cooling System

  • Jacket water pump, gear driven, centrifugal
  • Radiator sight gauge
  • Blower fan and fan drive with guards
  • Thermostats and housing
  • Coolant drain valve
  • Radiator, package mounted

Exhaust System

  • Exhaust manifold - dry

Fuel System

  • Fuel priming pump
  • Primary fuel filter w/integral water separator and secondary filter, spin on
  • Wide skid base

Generators and Generator Attachments

  • Insulation system, Class H
  • Brushless, self-excited 2/3 pitch (600V uses Internal excitation (IE))
  • Voltage regulator (single phase sensing)
  • IP23 Protection

Governing System

  • Cat electronic governor (ADEM A4)

Lube System

  • Oil filler and dipstick
  • Lubricating oil
  • Shallow oil pan
  • Oil filter, spin on
  • Fumes disposal to front of radiator
  • Oil cooler
  • Oil drain with valve

Mounting System

  • Includes lifting provisions and termination points for coolant and lube oil drain lines
  • Captive linear vibration isolators between base and engine-generator

Protection

  • Safety shutoff - Overspeed
  • Safety shutoff - High water temperature
  • Safety shutoff - Low oil pressure

Starting/Charging System

  • 24-volt electric starting motor
  • 24V, 45 Amp Charging alternator

General

  • Vibration damper

Telematics

  • Cat® Product Link™ PL444 cellular

Optional Equipment

Bases, Mounting & Fuel Tanks

  • Integral extended 24 hrs tank
  • Audio & visual fuel alarm (@90% fuel level)
  • Fuel tank pill pipe & lockable cap

Circuit breaker

  • 400A LS/I
  • 600A LS/I
  • 1200A LSI
  • 600A LSI
  • 1200A LS/I
  • Auxiliary contacts
  • 400A LSI
  • 800A LSI
  • 800A LS/I

Control System

  • Twist release, Red button emergency stop
  • Product link remote monitoring hardware
  • Volt free contacts
  • Ground fault relay
  • 20A GFCI (Ground Fault Circuit Interrupter)
  • Audible alarm Gp
  • 100A Load center

Enclosures

  • E-Stop
  • AC & DC Source lights
  • Sound attenuated Level 2 enclosure (White)

Exhaust System

  • 6" Muffler - 25 dBA attenuation
  • Flexible exhaust connection
  • Manifold and turbocharger guards

Generator

  • Permanent magnet excitation (PMG) generator
  • Space heater

Starting System

  • Standard battery set: 1000 CCA, 90 amp/hr.
  • Battery charger (UL Certified)
  • Jacket water heater

General

  • CSA Certification
  • Extended Service Coverage
  • Generator test report
  • UL2200 Certification
360° Interior View (HTML)
360° Exterior View (HTML)
{Promo Placeholder}
{Promo Placeholder}

Similar Products