D40 GC Generator Set
Description
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Manufacturer: CAT
Brochures & Links
Specifications
Download Specification Sheets
| Standby Rating | 40 ekW |
|---|---|
| Frequency | 60 Hz |
| Emissions/Fuel Strategy | U.S. EPA Tier 3 Certified |
| Voltage | 208 to 600 Volts |
| Speed | 1800 rpm |
| Duty Cycle | Standby |
| Engine Model | C4.4, In-line 4, 4-cycle diesel |
|---|---|
| Bore | 4.1 in105 mm |
| Stroke | 5 in127 mm |
| Displacement | 269 in4.4 l |
| Compression Ratio | 18.2:1 |
| Aspiration | Turbocharged |
| Fuel System | Common Rail |
| Governor Type | Mechanical, ADEM™A4 |
| Length - Maximum | 77.2 in1962 mm |
|---|---|
| Width - Maximum | 43.3 in1100 mm |
| Height - Maximum | 48 in1220 mm |
| Dry Weight - Genset (maximum) | 1847 lb838 kg |
Key Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.2 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- UL 2200 Listed
- ULC Certification Available
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Equipment
Standard Equipment
Air Inlet
- Standard air filter
Circuit breakers
- Second circuit breaker box
- Power terminal strip
Control Panel
- GCCP 1.2 Control panel
Exhaust System
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
Fuel System
- Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
Cooling System
- Caterpillar extended life coolant
- Radiator and cooling fan with guards
- Coolant drain line with valve
- Fan drive, battery charging alternator drive
- Radiator stone guard
Governing System
- Mechanical and electrical governing system - model dependent
Lube System
- Lubricating oil
- Oil drain line with valve
Control Panels
- NFPA110 bundle
- Fuel level alarm
- Oil temperature gauge and sender
- Remote E-stop button
- Volt free contacts genset run and common alarm
- Discrete I/O module
- Audible alarm
- Ground fault relay
- Remote annunciator module
- Overload shutdown via breaker
- Low coolant level shutdown
- Fuel level reading
- Protective devices:
- Low coolant temperature alarm
General
- Engine and alternator pre-paint, Caterpillar yellow
Starting/Charging System
- Batteries
- 24V battery with rack and cables
Telematics
- Cat® Product Link™ PL444 cellular
Optional Equipment
Certificates
- IBC seismic and wind Certifications
Charging System
- Battery charger
Circuit breakers
- Power terminal strip
- Second circuit breaker box
Control Panels
- Ground fault relay
- Remote annunciator module
- Remote E-stop button
Enclosures
- Panel viewing window
- Sound attenuated enclosure, Level 2
- External emergency stop
Heating Elements
- Anti-condensation heater
- Coolant heater
- Lube oil sump heater
- Wiring for canopy space heater
- Jacket water heater
- Battery heater
Cooling System
- Radiator transition flange
Fuel System
- Emergency vent pipe
- 24 hrs Integral tank
- 5 Gallon fill containment
Mounting System
- Seismic vibration isolators
Exhaust System
- 10, 25 and 35 dBA silencer systems
- Overhead silencer mounting kit
Generators
- Permanent magnet excitation (PMG) generator
{Promo Placeholder}
{Promo Placeholder}
Similar Products