D550 GC (60 Hz) Generator Set

Share

Description

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Manufacturer: CAT

Brochures & Links

Specifications

Download Specification Sheets

Specifications

Standby Rating 550 ekW
Frequency 60 Hz
Emissions/Fuel Strategy U.S. EPA Tier 2 Certified
Voltage 480 to 600 Volts
Speed 1800 rpm
Duty Cycle Standby
Engine Model Cat® C18 In-line 6, 4-cycle diesel
Bore 5.7 in145 mm
Stroke 7.2 in183 mm
Displacement 1106 in³18.1 l
Compression Ratio 14.5:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel System MEUI
Governor Type ADEM™A4
Length - Maximum 196.1 in4980 mm
Width - Maximum 73.4 in1865 mm
Height - Minimum 79.1 in2009 mm
Height - Maximum 100.9 in2563 mm
Dry Weight - Genset (minimum) 8776.6 lb3981 kg
Dry Weight - Genset (maximum) 11464 lb5200 kg

Key Features

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR500 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to104°F (40°C)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

Designed to meet applicable global standards including ISO 8528, ISO 3046 and IEC 60034-1, with CSA, UL2200, IBC, NEMA and NFPA conformity available depending on configuration and market.

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Equipment

Standard Equipment

Air Inlet System

  • Standard air cleaner

Control Panel

  • GCCP 1.2

Cooling System

  • Jacket water pump, gear driven, centrifugal
  • Radiator, package mounted
  • Radiator sight gauge
  • Thermostats and housing
  • Blower fan and fan drive with guards
  • Coolant drain valve

Exhaust System

  • Exhaust manifold - dry

Fuel System

  • Fuel cooler

Base

  • Standard wide base

Generators and Generator Attachments

  • Insulation system, Class H

Governing System

  • Cat electronic governor (ADEM A4)

Lube System

  • Oil cooler
  • Oil drain with valve
  • Shallow oil pan
  • Oil filter, spin on
  • Fumes disposal to front of radiator
  • Oil filler and dipstick

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant and lube oil drain lines

Protection

  • Safety shutoff - Overspeed
  • Safety shutoff - Low oil pressure
  • Safety shutoff - High water temperature

Starting/Charging System

  • 24-volt electric starting motor
  • 24V, 45 Amp Charging alternator

General

  • Lifting eyes
  • Vibration damper

Telematics

  • Cat® Product Link™ PL444 cellular
  • Cat® Product Link™ PL444 cellular

Optional Equipment

Bases, Mounting & Fuel Tanks

  • Integral tank base, 24 hours, UL142
  • Fuel tank pill pipe & lockable cap
  • Audio & visual fuel alarm (@90% fuel level)
  • 5 Gallon Spill Containment
  • Overfill prevention valve
  • Extended tank base, 24 hours, UL142

Circuit breaker

  • Auxiliary contacts
  • Single and multi manual breakers

Control System

  • 20A GFCI (Ground Fault Circuit Interrupter)
  • Twist release, Red button emergency stop
  • Product link remote monitoring hardware
  • 100A Load center
  • Ground fault relay
  • Audible alarm Gp
  • Remote E-Stop button
  • Discrete I/O module
  • Earth (Ground) fault relay

Enclosures

  • AC & DC Source lights
  • E-Stop
  • Sound attenuated level 2

Exhaust System

  • Flexible exhaust connection
  • Manifold and turbocharger guards
  • 8" Muffler - 25 dBA / Enclosure silencer

Generator

  • Space heater
  • Permanent magnet excitation (PMG) generator

Starting System

  • Standard battery set: 1000 CCA, 90 amp/hr.
  • Battery charger (UL Certified)
  • Jacket water heater
  • Oversize battery set, 1400 CCA, 200 amp/hr

General

  • CSA Certification
  • UL2200 Certification

Circuit breakers

  • Auxiliary contacts
  • Neutral bars

Cooling System

  • Jacket water heater with pump
  • Coolant heater
  • Stone guards

Base / Fuel Tank

  • Audio & visual fuel alarm

Starting and Charging

  • Oversize battery set
  • Battery disconnect switch
  • 5 Amp Battery charger
  • Standard battery set

Certifications

  • UL2200 Listed
  • CSA 22.2
  • IBC Seismic

Lube System

  • Manual sump pump