Specifications

Maximum Rating 500 ekW
Minimum Rating 400 ekW
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 208 to 600 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime
Engine Model C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 5.4 in137.2 mm
Stroke 6.75 in171.4 mm
Displacement 927.56 in³15.2 l
Compression Ratio 16.1:1
Aspiration Air to Air Aftercooled
Fuel System MEUI
Governor Type Adem™A4
Length - Maximum 168.2 in4273 mm
Width - Maximum 81 in2058 mm
Height - Maximum 82.4 in2092 mm

Key Features

Cat Generator Set Package

        

  • Cat generator set packages have been fully prototype tested
  •     

  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  •     

  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

        

  • Reliable, rugged, durable design
  •     

  • Field-proven in thousands of applications worldwide
  •     

  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

A-Frame Alternator

        

  • Superior motor starting capability minimizes need for oversizing alternator
  •     

  • Designed to match performance and output characteristics of Cat diesel engines
  •     

  • Robust Class H insulation

GCCP 1.3 Control Panel

        

  • User-friendly interface and navigation
  •     

  • Scalable system to meet a wide range of installation requirement
  •     

  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

        

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  •     

  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

UL2200 Listed; CSA 22.2; Certification of Compliance – IBC Seismic; Dual IBC & HCAI

One Safe Source

        

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  •     

  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  •     

  • Each generator set package is tested before leaving the Caterpillar facility
  •     

  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

        

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  •     

  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Equipment

Standard Equipment

Air System

  • Turbocharger
  • Air cleaner - Non canister disposable paper filter
  • Aftercooler core

Air Inlet

  • Air cleaner

Control Panel

  • GCCP 1.3
  • GCCP Genset Controller

Cooling

  • Package mounted radiator

Cooling System

  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant
  • Radiator and cooling fan with guard

Exhaust

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied
  • Exhaust flange outlet

Fuel

  • Primary fuel filter with integral water separator
  • Secondary fuel filters
  • Fuel priming pump

Fuel System

  • Engine fuel transfer pump
  • Flexible fuel lines
  • Fuel cooler
  • Fuel priming pump
  • Primary fuel filter w/integral water separator and secondary filter

Generator

  • IP23 Protection
  • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
  • Matched to the performance and output characteristics of Cat engines

Power Termination

  • Busbar

Mounting

  • Rubber vibration isolators

Generator and Attachments

  • Segregated low voltage (AC/DC) wiring panel
  • Optional LC Frame generator - IP23 Protection
  • Power center, IP22
  • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • Integrated voltage regulator (IVR)
  • A Frame generator - IP21 Protection

Governing System

  • Cat electronic governor (ADEM A4).

Lube System

  • Oil drain valves
  • Oil cooler

Mounting System

  • Captive linear vibration isolators between base and engine-generator includes lifting provisions and termination points for coolant and lube oil drain lines

Starting/Charging

  • 24 Volt battery with rack and cables
  • 24 volt starting motor
  • Batteries

General

  • Engine and alternator pre paint, Caterpillar yellow
  • Paint - Caterpillar yellow except rails and radiators gloss black

Optional Equipment

Air Inlet System

  • Single element air cleaner
  • Dual element air cleaner

Exhaust

  • Industrial, residential, critical mufflers

Certifications

  • Global certification for CIS
  • EU Certificate of Conformance (CE)

Generator

  • Anti-condensation heater
  • Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
  • Oversize and premium generators

Circuit breakers

  • 4 Pole (IEC-100% rated) Circuit breakers - Package mounted
  • Power terminal strip
  • 4 Pole (IEC-100% rated) Circuit breakers - Motorised
  • Shunt trip for IEC circuit breaker
  • Padlockable circuit breaker device
  • Auxiliary contacts, circuit breaker
  • 3 Pole (IEC-100% rated) Circuit breakers - Motorised
  • 3 Pole (IEC-100% rated) Circuit breakers - Package mounted

Power Termination

  • Circuit breakers, IEC compliant
  • Circuit breakers, UL listed

Control Panels

  • Remote annunciator module
  • Local alarm horn
  • Local annunciator
  • Oil temperature displays
  • GCCP 1.4
  • Volt free contacts
  • Protective devices: Earth fault relay ; Earth leakage Ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor

Starting/Charging

  • Charging alternator
  • Battery chargers
  • Oversize batteries
  • Heavy duty starting system
  • Jacket water heater

Cooling System

  • Low coolant temperature alarm
  • Stone guards
  • Radiator duct flange

Enclosures

  • Sound attenuated enclosures
  • High ambient sound attenuated enclosures

Exhaust System

  • Engine mounted muffler
  • 6 and 8 inch elbow kit
  • Manifold and turbocharger guards
  • End in/end out mufflers - 10, 25 and 35 dBA attenuation
  • 6 and 8 inch flange GP
  • Flexible exhaust fittings

Fuel System

  • Fuel transfer system controls
  • Manual fuel transfer pump
  • Optional BS799 Compliant Integral - Dual wall fuel tank base

General

  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • Sound attenuated, weather protective or high ambient weather protective enclosure
  • EU Certificate of Conformance (CE)
  • Single or dual wall integral fuel tanks
  • CSA Certification
  • EEC Declaration of Conformity
  • Narrow, wide or skid base
  • Integral & sub-base UL listed dual wall fuel tanks
  • Automatic transfer switches (ATS)
  • UL 2200 package
  • The following options are based on regional and product configuration:
  • Single or dual wall sub-base fuel tanks

Generator and Attachments

  • Oversize LC frame generator
  • Oversize A Frame generator
  • CIP A Frame generator
  • LC frame generator
  • LC frame CIP generator
  • Ingress protection
  • Permanent magnet excitation (PMG) generator
  • Space heaters

Lube System

  • Manual sump pump

Mounting System

  • Narrow skid base - replaces standard fuel tank base

Special Test / Reports

  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8 power factor

Starting / Charging System

  • 5 Amp single Battery charger
  • Battery disconnect switch
  • Jacket water heater
360° Exterior View (HTML)
360° Exterior View (HTML)
{Promo Placeholder}
{Promo Placeholder}

Similar Products