C27 | 750 eKW 60 Hz Generator Set
Description
The C27 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 680 to 800 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and to take on 100 percent rated load in one step. The C27 is certified as a low fuel consumption system as well as having a certificate for EPA Stationary Emergency (Tier 2). Seismic certification is also available for selected models, ensuring your generator sets are equipped for that unexpected disturbance. The integrated control system, including ATS and switchgear, ensures a consistent power supply and connection to your fleet through on-site and remote monitoring options. Our EMCP 4 control panel features a user-friendly interface and puts your management and diagnostics tools in one location. The EMCP 4.4 controller provides multi generator set paralleling capability, allowing you to use multiple generator sets for increased power output and improved reliability. It’s not just quality that matters but customization, choose from a broad range of accessories and bolt-on system expansion attachments. Discover our upgradeable packaging options to work with your spatial restrictions and environmental conditions. Our C27 generator sets are developed for such prerequisites, so that you can meet your specific power needs. Build in additional safety features with the UL 2200 and CSA certified package options.
Manufacturer: CAT
Brochures & Links
Specifications
Download Specification Sheets
- C27, 60 Hz, 750 ekW Standby 680 ekW Prime, Low Fuel Consumption Spec Sheet
- C27, 60 Hz, 750 ekW Standby 680 ekW Prime, U.S. EPA Emergency Stationary (Tier 2) Spec Sheet
| Maximum Rating | 800 ekW |
|---|---|
| Minimum Rating | 635 ekW |
| Emissions/Fuel Strategy | Low Fuel, Tier 2 Nonroad Equivalent |
| Voltage | 208 to 600 Volts |
| Frequency | 60 Hz |
| Speed | 1800 rpm |
| Duty Cycle | Standby, Prime |
| Engine Model | C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel |
|---|---|
| Bore | 5.4 in137.2 mm |
| Stroke | 6 in152.4 mm |
| Displacement | 1649.47 in³27.03 l |
| Compression Ratio | 16.1:1 |
| Aspiration | TA |
| Fuel System | MEUI |
| Governor Type | Adem™A4 |
| Length - Maximum | 184 in4674 mm |
|---|---|
| Width - Maximum | 67.8 in1723 mm |
| Height - Maximum | 85.1 in2162 mm |
Key Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP 4 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- UL 2200
- CSA
- IBC seismic certification
- OSHPD pre-approval
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Equipment
Standard Equipment
Air Inlet
- Air cleaner; single element canister type with service indicator
Control Panel
- EMCP 4.2B
- Digital Indicators
- Communications
- Warning/shutdown Indicators
- Programmable protective relaying functions
- Features include:
Cooling System
- Caterpillar extended life coolant
- Radiator sized to 50 degrees C
- Coolant drain line with valve terminated on edge of base
- Fan and belt guards drive
- ATAAC
- Coolant level sensor
Exhaust System
- 203 mm (8 in) ID round flanged outlet
- Exhaust manifold - dry
Fuel System
- Flexible fuel lines - installed
- Secondary fuel filters
- Primary fuel filter with integral water separator
- Electric fuel priming pump
- Fuel cooler
Generators and Attachments
- Integrated voltage regulator (IVR) includes
- SR5 Permanent magnet excitation (PMG) (PM)
- For EPA Stationary Emergency (EPA Tier 2 Emissions) configurations:
- For Low BSFC configurations:
- Busbar connections:
Lube System
- Gear type lube oil pump
- Oil filter, filler and dipstick
- Integral lube Oil cooler
- Lubricating oil
- Oil drain lines and valve
- Fumes disposal - open crankcase ventilation routed to front of package
- Standard volume oil pan - 68 Ltr
Mounting System
- Rails - engine/generator/radiator mounting
- Rubber anti-vibration mounts - shipped loose
Starting and Charging System
- Battery, rack and cables - shipped-loose
- Charging alternator 45A
- 24-volt electric starting motor
- Battery disconnect switch
General
- Paint - Caterpillar yellow with high gloss black rails & radiator
- Flywheel and flywheel housing-SAE No. 0 and SAE No. 18
- SAE standard rotation
- Right hand servicing
Optional Equipment
Air Inlet System
- Standard air cleaners
- Dual element air cleaners
- Heavy duty air cleaners
Starting / Charging System
- Jacket water heaters
- 24 Volt electric start motors - Heavy duty
- 20 Amp enclosure Battery chargers
- 10 Amp Battery chargers
- 24 Volt battery set - Dry
- Air starting motor with control and silencer
- Space heater
Circuit breakers
- 400, 800, 1200, 1600, 2000, 2500, 3000 Amp, 3 pole, UL-100% rated Circuit breakers
- 2000 Amp, 3 pole, IEC rated Circuit breakers
- 800 Amp, 4 pole, IEC rated Circuit breakers
Control Panels
- Side extension box
- Load share module
- Annunciator modules
- Vandal proof panel cover
- Cable shroud - Bottom mounted
- Remote mounted panel harness mounting kit
- Auxiliary box options
- Remote mounting harness
- Remote DIO module
- Cat connect telematics
- Modbus monitor local packages
- Cable shroud - Top mounted
- Remote mounted circuit breaker terminals
- EMCP 4.3, EMCP4.4
- Remote annunciator module
- Installed DIO module
Cooling System
- Extended life coolant
- High ambient radiator
- Certified radiator
- Standard radiator
- Radiator duct flange
Enclosures
- Panel bracket
- Enclosure with lifting base or fuel tank
- Cold weather bundle
- Special Sound attenuated enclosure
- Enclosure louvers
- Enclosure colors
- AC distribution panel, lights and outlet
- Enclosure lighting
- Enclosure fuel tank options
Exhaust System
- Guard and shield system
- Flexible fittings
- Exhaust through the wall kit
- Elbows
- Mufflers
- Flanges
Generator and Attachments
- 60 Hz standard generators
- 60 Hz premium generators
Lube System
- Oil level regulator
- Prelube pumps
Mounting System
- Spring type vibration isolators
- Mounting base type
- IBC vibration isolators
- Puck style low efficiency isolators
Power Connections
- Center post busbars
- Neutral grounding connection
- Cable entry - right/left/rear
- Power connections - Right / Left / Rear
Special Tests / Reports
- PGS Test report @ 0.8 power factor
- Standard engine test
- Special CSA test Certification
- IBC seismic Certifications
- OSHPD seismic Certifications
- PGS Test report @ 1.0 power factor
- Torsional vibration analysis report
- Generator test report
General
- US aid emblem
- Miscellaneous inspection
- SGS Inspection
- Special paint
Similar Products
Request a Quote
A MiltonCAT sales rep will get back to you shortly.
Quote form not yet configured. Set MILTONCAT_GP_QUOTE_FORM_ID to the Gravity Forms form ID; page context is auto-prefilled via the mc_* dynamic-population parameters.